Vibration dampers
APPLICATION:
VORTX Dampers respond to wind induced line vibration that is characterized by high frequency, low amplitude motion due to aeolian vibration. The VORTX damper with Large and Small weights can achieve greater power dissipation and frequency response performance than "symmetrical weight" Stockbridge damper designs.
VORTX Dampers can be clamped directly onto most aluminum based conductors including ACSR, AAC, AAAC and ACAR. PLP® Protector Rods should be considered for applications on aluminum conductors with relatively soft outer aluminum strand construction such as ACSS. Protector rods are designed to reduce direct clamping stress on cable vulnerable to surface or core damage – this
includes fiber optic cable designs such as ADSS and OPGW.
Generally as conductors and cables increase in size they tend to vibrate at lower frequencies. The VORTX Damper is more effective for larger size conductors while the Spiral Vibration Dampers (see Helical fittings ) are generally more effective for the smaller diameter cables that can vibrate at much higher frequencies.
The degree of protection required on a specific line depends upon a number of factors such as: *line design, local climate, tension, exposure to wind flow, and line vibration history in the area*. With assistance from your local PLP Sales Representative, the necessary information can be assembled for review and followed up with detailed PLP recommendations for your system.
VORTX Dampers meet the requirements of International Standard IEC 61897.
* Please collect all neccessary information for preparing calculation
Spacer-damper for triple bundle conductor
APPLICATION: these spaceres are used to maintain the subconductors spacing of triple bundle and to ensure vibration damping in conductors.
Spacer, for triple bundle conductor
APPLICATION: these spacers are used to maintain the subconductors spacing of triple bundle.
Clamps
APPLICATION: these clamps are:
1. used to assemble a damping loop
2. parts of flexible spacers for ACSR 8-525 or AL877 conductors.
Protection
APPLICATION: these designes are used as a protection against go up a pole of the high voltage line.
Full offer you coudl find in Chapter 6 - Dampers, spacers, conductor & tower protection .